Punch List / Issues
| # | Title | Location | Assigned To | Form | Status | Score | Reported | Resolved | |
|---|---|---|---|---|---|---|---|---|---|
| 1 |
CMDF1 Hole on East Wall Floor
Issue #6394: Concrete has a hole on the East Wall 66 1/2 inches from the South w… |
RPL10
– 10CMDF1
CMDF1 |
DPR | 6394 | Open | – | 04/30/2026 | – | |
| 2 |
GSIDFNX05 MOFE Door
The door to the MOFE appears to be coming off of the top hinge. The door is not … |
RPL10
GSIDFNX05 |
DPR | 6395 | Open | – | 04/30/2026 | – | |
| 3 |
GSIDFNX5 Labeling Conflict
Issue #6393: There is a conflict between the labeling of the Micro duct and the … |
RPL10
IDFNX5 |
Mortenson | 6393 | Open | – | 04/30/2026 | – | |
| 4 |
CMDF2 South and West wall vertical ladder rack blocked by EPMS/BAS Conduit
EPMS/BAS conduit run is blocking the vertical ladder rack locations on the South… |
RPL10
– 10CMDF2
South & West wall above horizontal ladder rack |
DPR | 6391 | Open | – | 04/30/2026 | – | |
| 5 |
GSEF1 West Wall Ladder Rack
Vertical and Horizontal Ladder rack locations will block access to Security Cont… |
RPL10 – 10GSEF1 | DPR | 5084 | Open | – | 04/14/2026 | – | |
| 6 |
GSEF 1/2 Ladder Runway Cross-over Support
Ladder rack crossovers in GSEF 1/2 exceed the maximum allowable unsupported span… |
RPL10 – 10GSEF1 | DPR | 5281 | Open | – | 04/14/2026 | – | |
| 7 |
CMDF2 South wall Vertical Ladder Rack
Vertical Ladder Rack will be in the way of the boxes on the wall. Pictures added… |
RPL10 – 10CMDF2 | DPR | 5174 | Open | – | 04/13/2026 | – |